Aprilaire Dehumidifier 1700 User Manual

Dehumidifier  
Service  
Access  
Port  
Filter  
Access  
Humidity  
Control  
Filter  
Access  
Inlet  
Outlet  
Drain  
Wiring  
Access  
Wire  
Routing  
Port  
On/Off  
Switch  
Safety and Installation Instructions  
Model 1700  
INSTALLER – PLEASE NOTE!  
1. Installation must conform to all applicable codes.  
3. For protection of the compressor, unit must be  
transported and installed in an upright position.  
If the unit was shipped or stored on its side, a 24 hour  
settling period is required before running the unit.  
2. A dedicated 15 Amp circuit is required for proper  
operation of the dehumidifier. If a dedicated circuit  
is not available, do not install unit.  
TABLE OF CONTENTS  
Safety Instructions . . . . . . . . . . . . . . .2  
Overview . . . . . . . . . . . . . . . . . . . . . . .2  
Specifications . . . . . . . . . . . . . . . . . . .2  
Location Notes . . . . . . . . . . . . . . . . . .2  
Ducting . . . . . . . . . . . . . . . . . . . . . . . .3  
Drain Line . . . . . . . . . . . . . . . . . . . . . .3  
Hanging . . . . . . . . . . . . . . . . . . . . . . .3  
Installations  
Whole House . . . . . . . . . . . . . . . . . . .4  
Localized . . . . . . . . . . . . . . . . . . . . . . .6  
Whole House / Localized  
Convertible . . . . . . . . . . . . . . . . . . . . .8  
Float Switch . . . . . . . . . . . . . . . . . . .12  
Dip Switch Definitions . . . . . . . . . . .12  
System Checkout . . . . . . . . . . . . . . .13  
Troubleshooting . . . . . . . . . . . . . . . .14  
Sequences  
of Operations . . . . . . . . . . .Back Cover  
Ventilation and Fan Cycling . . . . . . .10  

Expand Contents

DUCTING  
The Aprilaire Dehumidifier is supplied with two  
8” round collars. These are packaged with a  
condensate trap inside the unit behind the filter  
access panel. When installing the collar make sure  
the foam seal uniformly contacts the cabinet and  
secure with 4 screws (not included). UL approved  
8” diameter, insulated flexible duct is recommended  
for all connections. Rigid metal duct may be used.  
The duct should be capable of handling at least  
2” w.c. of positive and 0.75” w.c. of negative  
pressure. All joints and seams must be sealed.  
For optimal moisture removal, airflow should be at or above  
275 CFM.  
The total static pressure across the dehumidifier must not  
exceed 0.8” w.c. Check all pressures with the HVAC fan on.  
• The outlet from the dehumidifier to the HVAC supply duct must be  
located at least 6” downstream of the cooling coil.  
• If connected to HVAC ductwork, the dehumidifier inlet must be located  
at least 6” upstream of the HVAC system air cleaner. This will prevent  
any trapped particulates from being drawn into the dehumidifier.  
• If UV Germicidal lamps are installed in the HVAC system, use  
appropriate methods to protect the flexible duct from the UV light.  
Design air flow is 275 CFM @ 0.6” w.c. This is  
equivalent to 70 ft. of 8” duct on the inlet and  
outlet side of the dehumidifier. Elbows, turns and  
the static pressure of the HVAC equipment will  
affect the airflow through the dehumidifier.  
• If air noise is a problem, install at least 5 feet of acoustical flexible  
duct on the outlet and inlet of the dehumidifier.  
DRAIN LINE  
The included condensate trap  
must be installed to the Model  
1700. Use PVC primer and  
cement to connect the trap to the  
drain outlet on the Model 1700.  
The drain outlet is located near  
the On/Off toggle switch. Note  
orientation of trap prior to  
FIGURE 1  
Drain Outlet  
1/2”  
Drain Trap  
21/2”  
High Side  
Low Side  
90-961  
cementing. The high side of the  
trap mates with the Model 1700. The adjustable legs on  
the Model 1700 must be disengaged approximately 1” to  
accommodate the trap. Complete the assembly by piping  
the trap to a drain. The trap must be primed with water  
prior to start-up.  
FIGURE 2  
If the 1700 is installed in an attic or in an area where  
flooding is a potential problem, it should be installed in a  
secondary drain pan with a condensate overflow safety  
switch. See page 12 for condensate overflow safety  
switch wiring.  
3“ MIN  
CLEARANCE FOR  
ACCESS PANEL  
TOP VIEW  
20” MINUMUM  
CLEARANCE FOR FILTER  
(EITHER SIDE)  
HANGING  
FILTER  
If hanging the unit, use two unistruts to support the base  
on the outside edges of the feet locations. There must  
be at least 20” of clearance in front of one of the filter  
access doors to allow removal of the filter.  
6" MIN CLEARANCE FOR FILTER  
90-970  
3
WHOLE HOUSE INSTALLATION AND OPERATION  
In this configuration the dehumidifier will pull air from the return duct. The air passes through the dehumidifier, where moisture is  
removed, and then returned to the HVAC system downstream of the cooling coil in the supply plenum. This installation is used  
when the HVAC unit conditions the area where dehumidification is needed. Connection to the HVAC unit for the primary living  
space or basement HVAC unit is ideal for this installation.  
REQUIRED COMPONENTS  
OPTIONAL COMPONENTS  
1 – 6508 Normally Closed Power Open Damper  
Duct Work  
6506 Ventilation Damper  
24 VAC Transformer (10 VA minimum) for Ventilation Damper  
8052 Outdoor Temperature Sensor  
24 VAC Transformer (10 VA minimum)  
Thermostat Wire  
Normally Closed Condensate Overflow Safety Switch  
FIGURE 3 – DUCTING  
COOLING COIL  
6“ MIN  
AIR CLEANER  
6“ MIN  
SUPPLY  
AIRFLOW  
RETURN  
AIRFLOW  
OPTIONAL N.C.  
VENT CONTROL  
DAMPER  
HVAC UNIT  
(SEE PAGES 10-11)  
OPTIONAL  
OUTDOOR  
AIR INTAKE  
1700  
3‘ MIN  
N.C. BACKFLOW DAMPER  
90-945  
4
WHOLE HOUSE INSTALLATION AND OPERATION (CONTINUED)  
DEHUMIDIFIER  
CONTROL  
N.C. BACKFLOW  
FIGURE 4 – WIRING  
24 VAC  
(10 VA min)  
DAMPER  
TRANSFORMER  
THERMOSTAT  
HVAC EQUIPMENT  
R
R
C
G
C
G
W
Y
W
Y
See page 10 for ventilation control wiring instructions.  
See page 10 for fan cycling wiring instructions.  
See page 12 for float switch wiring instructions.  
90-962  
FIGURE 5 – SETTINGS  
SYSTEM SETUP  
Standard  
Fan Cycling  
Ventilation  
OFF  
ON  
OFF  
OFF  
OFF  
See pages 10-11  
OFF  
MODEL 70  
HVAC FAN  
MODEL 70  
HVAC FAN  
See pages 10-11  
See pages 10-11  
WHL HOUSE  
VENT-AUTO  
CONVERTIBLE  
VENT-TIMED  
OFF  
OFF  
OFF  
ON  
OFF  
CYCLE PERIOD  
Standard  
Fan Cycling  
Ventilation  
30 MIN.  
1 HOUR  
2 HOUR  
3 HOUR  
OFF  
ON  
OFF  
OFF  
See pages 10-11  
See pages 10-11  
See pages 10-11  
See pages 10-11  
See pages 10-11  
See pages 10-11  
See pages 10-11  
See pages 10-11  
30  
MIN.  
0
60  
MIN.  
MIN  
Standard  
Fan Cycling  
Ventilation  
OFF  
See pages 10-11  
See pages 10-11  
OFF  
TEST  
CYCLE TIME  
90-963  
5
LOCALIZED INSTALLATION AND OPERATION  
In this configuration the dehumidifier will pull air from an area in the home. The air passes through the dehumidifier, where  
moisture is removed, and then is returned to the area. This installation is used when the HVAC unit conditions an area other than  
where dehumidification is needed. An unconditioned basement or crawl space application is ideal for this installation.  
REQUIRED COMPONENTS  
OPTIONAL COMPONENTS  
None  
Duct Work  
24 VAC Transformer (10 VA minimum) for Ventilation Damper  
Thermostat Wire  
6506 Ventilation Damper  
8052 Outdoor Temperature Sensor  
Grilles  
Normally Closed Condensate Overflow Safety Switch  
FIGURE 6 – DUCTING  
OPTIONAL  
OUTDOOR AIR INTAKE  
OPTIONAL N.C.  
VENT CONTROL  
DAMPER  
COOLING COIL  
AIR CLEANER  
(SEE PAGES 10-11)  
SUPPLY  
AIRFLOW  
RETURN  
AIRFLOW  
HVAC UNIT  
TO GRILLE OR  
TO OPEN SPACE  
FROM GRILLE  
OR OPEN SPACE  
1700  
90-946  
6
LOCALIZED INSTALLATION AND OPERATION (CONTINUED)  
DEHUMIDIFIER  
CONTROL  
FIGURE 7 – WIRING  
THERMOSTAT  
HVAC EQUIPMENT  
R
C
G
R
C
G
W
Y
W
Y
See page 10 for ventilation control wiring instructions.  
See page 10 for fan cycling wiring instructions.  
See page 12 for float switch wiring instructions.  
90-964  
FIGURE 8 – SETTINGS  
SYSTEM SETUP  
Standard  
Fan Cycling  
Ventilation  
OFF  
ON  
OFF  
OFF  
OFF  
MODEL 70  
MODEL 70  
HVAC FAN  
HVAC FAN  
See pages 10-11  
See pages 10-11  
See pages 10-11  
WHL HOUSE  
VENT-AUTO  
CONVERTIBLE  
VENT-TIMED  
ON  
OFF  
ON  
ON  
ON  
OFF  
CYCLE PERIOD  
Standard  
Fan Cycling  
Ventilation  
30 MIN.  
1 HOUR  
2 HOUR  
3 HOUR  
OFF  
ON  
OFF  
OFF  
See pages 10-11  
See pages 10-11  
See pages 10-11  
See pages 10-11  
See pages 10-11  
See pages 10-11  
See pages 10-11  
See pages 10-11  
30  
MIN.  
0
60  
MIN.  
MIN  
Standard  
Fan Cycling  
Ventilation  
OFF  
See pages 10-11  
See pages 10-11  
OFF  
TEST  
CYCLE TIME  
90-965  
7
WHOLE HOUSE / LOCALIZED CONVERTIBLE INSTALLATION AND OPERATION  
In this configuration the dehumidifier will automatically switch between whole-house dehumidification when the HVAC  
equipment is on, and localized dehumidification when the equipment is off. This installation is used to dehumidify a whole house  
and a separate unconditioned space like an unfinished basement, or an area where circulation from that location throughout the  
entire house is undesirable.  
REQUIRED COMPONENTS  
OPTIONAL COMPONENTS  
2 – 6508 Normally Closed Power Open Damper  
2 – 6608 Normally Open Power Closed Damper  
Duct Work  
6506 Ventilation Damper  
24 VAC Transformer (10 VA minimum) for Ventilation Damper  
8052 Outdoor Temperature Sensor  
24 VAC Transformer (40 VA minimum)  
Thermostat Wire  
Normally Closed Condensate Overflow Safety Switch  
FIGURE 9 – DUCTING  
OPTIONAL  
OUTDOOR AIR INTAKE  
COOLING COIL  
AIR CLEANER  
OPTIONAL  
N.C. DAMPER  
6“ MIN  
6“ MIN  
3‘ MIN  
SUPPLY  
AIRFLOW  
RETURN  
AIRFLOW  
HVAC UNIT  
N.C. DAMPER  
N.C. DAMPER  
SUPPLY TO  
UNCONDITIONED  
SPACE  
RETURN FROM  
UNCONDITIONED  
SPACE  
1700  
N.O. DAMPER  
N.O. DAMPER  
90-947  
8
WHOLE HOUSE / LOCALIZED CONVERTIBLE INSTALLATION AND OPERATION (CONTINUED)  
DEHUMIDIFIER  
CONTROL  
FIGURE 10 – WIRING  
24 VAC  
(40 VA min)  
DEHUMIDIFIER SYSTEM DAMPERS  
TRANSFORMER  
THERMOSTAT  
R
HVAC EQUIPMENT  
R
C
C
G
WIRE NUT  
G
W
Y
W
Y
See page 10 for ventilation control wiring instructions.  
See page 10 for fan cycling wiring instructions.  
See page 12 for float switch wiring instructions.  
90-966  
FIGURE 11 – SETTINGS  
SYSTEM SETUP  
Standard  
Fan Cycling  
Ventilation  
OFF  
ON  
OFF  
OFF  
ON  
OFF  
OFF  
ON  
ON  
OFF  
OFF  
ON  
MODEL 70  
HVAC FAN  
MODEL 70  
HVAC FAN  
WHL HOUSE  
VENT-AUTO  
CONVERTIBLE  
VENT-TIMED  
OFF  
OFF  
CYCLE PERIOD  
Standard  
Fan Cycling  
Ventilation  
30 MIN.  
1 HOUR  
2 HOUR  
3 HOUR  
OFF  
ON  
OFF  
OFF  
See pages 10-11  
See pages 10-11  
See pages 10-11  
See pages 10-11  
See pages 10-11  
See pages 10-11  
See pages 10-11  
See pages 10-11  
30  
MIN.  
0
60  
MIN.  
MIN  
Standard  
Fan Cycling  
Ventilation  
OFF  
See pages 10-11  
See pages 10-11  
OFF  
TEST  
CYCLE TIME  
90-965  
9
VENTILATION / FAN CYCLING SETTINGS  
The Aprilaire Dehumidifier has the option  
to monitor HVAC heating, cooling and fan  
calls to assure the HVAC fan has  
OPTIONAL  
VENTILATION  
DAMPER  
FIGURE 12  
DEHUMIDIFIER  
CONTROL  
24 VAC  
(10 VA min)  
operated a predetermined amount of  
time each 1/2, 1, 2 or 3 hours. The  
dehumidifier can also open a normally  
closed damper in an outdoor air intake to  
ventilate during this predetermined  
amount of time. This feature will  
function even if the dehumidifier is  
turned off at the dehumidifier or Model  
70 Living Space Control. The only way to  
disable this feature is by turning the  
Cycle Time setting to OFF or turning  
power off at the On/Off switch.  
TRANSFORMER  
THERMOSTAT  
R
HVAC EQUIPMENT  
R
C
C
G
WIRE NUT  
G
W
Y
W
Y
OPTIONAL OUTDOOR  
TEMPERATURE SENSOR  
(Model 8052)  
90-968  
First, set the 1/2, 1, 2 or 3 hour period by setting the CYCLE PERIOD dip switches to determine  
how often the dehumidifier should look to ventilate or cycle the HVAC fan.  
(shown set  
to 1 hour)  
FIGURE 13  
CYCLE PERIOD  
Next, use the CYCLE TIME dial to determine how long during every cycle period the HVAC fan  
30 MIN.  
should operate. Adjust the dial from OFF to between 1 to 60 minutes. This will give you HVAC fan  
operation from 1 to 60 minutes every 1/2, 1, 2 or 3 hours. A call for heat, cooling or fan from the  
HVAC equipment will often satisfy the run time requirement. If not, the dehumidifier will turn on  
the HVAC fan to assure that the cycle time is met. For example: If the home requires  
ventilation of 20 minutes every two hours set the CYCLE PERIOD Dip Switch for 2 hours  
to ON and rotate the CYCLE TIME to 20 minutes. If the HVAC equipment only has to run  
for 10 minutes, the dehumidifier will turn on the HVAC fan for 10 minutes at the end of  
the 2 hours to assure the ventilation / fan cycling time.  
1 HOUR  
2 HOUR  
3 HOUR  
90-783C  
(shown set to  
30 minutes)  
FIGURE 14  
30  
MIN.  
0
60  
MIN.  
MIN  
Finally, if using the Ventilation Damper, determine if the ventilation should be restricted based  
on outdoor temperature. Set the VENT-AUTO / VENT-TIMED dip switch to VENT-AUTO  
(see Figure 15) to prevent opening the ventilation damper if the outdoor air is above 100°F,  
below 0°F or except with a heat call between 20°F and 0°F. In the VENT-TIMED setting the  
ventilation damper is activated regardless of outdoor conditions. Note: The Outdoor  
Temperature Sensor (Model 8052) must be installed for this to work.  
OFF  
CYCLE TIME  
TEST  
90-783C  
FIGURE 15  
SYSTEM SETUP  
OFF  
ON  
MODEL 70  
MODEL 70  
You can also check the wiring of the dehumidifier to the HVAC equipment. If you rotate the  
CYCLE TIME dial to TEST, the HVAC fan should come on and the Ventilation Damper  
(if equipped) should open. DO NOT leave the CYCLE TIME in TEST.  
HVAC FAN  
HVAC FAN  
WHL HOUSE  
VENT-AUTO  
CONVERTIBLE  
VENT-TIMED  
90-969  
10  
VENTILATION / FAN CYCLING SETTINGS (CONTINUED)  
This installed option allows outside air to be combined with  
the fan cycling feature from the dehumidifier, provided the  
outside air temperature is in the acceptable range (0-100°F).  
Note: The dehumidifier can control the HVAC fan to provide  
fan cycling, regardless of whether or not an outdoor  
ventilation duct is installed.  
NORTH, EAST  
OR WEST SIDE  
OF HOME  
FIGURE 16  
OUTDOOR  
TEMPERATURE  
SENSOR  
SENSOR  
SENSOR  
BRACKET  
®
• An Aprilaire Normally-Closed Damper (Model 6506) should  
OUTDOOR  
TEMPERATURE SENSOR  
LEADS  
ABOVE EXPECTED  
SNOW LINE  
be installed in the outside air intake. It should be wired to the  
terminals labeled “VENT DAMPER” on the dehumidifier  
control board. Follow all installation instructions supplied  
with the damper. Refer to each installation for ducting.  
B2202617-D  
FIGURE 17  
• The Outdoor Temperature Sensor (Model 4278) should be  
installed outside in a shaded location (Figure 16) or in an  
outside air intake duct, but no more than 3 feet from the  
outside (Figure 17).  
CENTER LINE  
36" MAX.  
• The Outdoor Temperature Sensor is not affected by wire  
length. However, do not route the wire alongside wires  
carrying high voltage (115 VAC or greater), as interference  
may occur.  
OUTSIDE WALL  
B2202617-E  
• Connect the wires from the sensor to the terminals labeled “ODT SENSOR” on the dehumidifier.  
See Figure 12 for terminal locations.  
VENTILATION GUIDELINES  
TABLE 1 – Air Cycling Time Setting (min./hr.)  
Bedrooms  
1. Based on ASHRAE 62.2 ventilation  
requirement.  
House Size  
2. Based on outside air duct of 6”  
dia., 20’ long flex duct, 0.15” w.c.  
static pressure at outdoor air duct.  
(square feet)  
2
3
4
5
1000-1500  
1501-2000  
2001-2500  
2501-3000  
3001-3500  
20  
25  
25  
30  
30  
25  
30  
30  
35  
35  
30  
30  
35  
40  
40  
35  
35  
40  
40  
45  
3. Based on ‘Cycle Period’ being in  
the default (1 hour) position.  
4. A longer outside air duct and/or  
lower static pressure will require a  
longer Ventilation Time.  
As an example, for a 2,500 square foot home with 3 bedrooms, set the cycle time to 30 minutes of ventilation per one-hour cycle.  
A longer outdoor air intake duct or lower return static pressure will increase the ventilation time required. Additionally, local  
codes may affect the setting.  
11  
FLOAT SWITCH  
If the Model 1700 is installed in an attic, the unit should be  
placed in a drain pan with a normally closed condensate overflow  
safety switch (also known as a float switch). The float switch  
should be wired to the float switch terminals on the dehumidifier  
control board. See Figure 18. Remove the jumper at the float  
switch terminals. The compressor is disabled when the float  
switch is open. The Model 1700 will continue to ventilate when  
the float switch is open.  
FIGURE 18  
LOW VOLTAGE NORMALLY  
CLOSED FLOAT SWITCH  
90-968A  
DIP SWITCH DEFINITIONS  
MODEL 70 – OFF/ON (SYSTEM SETUP SWITCH #1):  
WHL HOUSE / CONVERTIBLE (SYSTEM SETUP SWITCH #3):  
Determines use of internal RH and temperature sensor or use  
of the RH and temperature sensor on the Living Space Control  
(Model 70).  
Determines when the dampers are powered open or closed.  
CONVERTIBLE position. The damper (DEH) terminals are  
actuated when the HVAC equipment is making a call for heat,  
cool or fan and the dehumidifier is making an internal blower  
call for air sampling or dehumidification.  
MODEL 70-OFF. Uses inlet RH and temperature sensor.  
MODEL 70-ON. Uses Living Space Control (Model 70)  
RH and Temperature Sensor.  
WHL HOUSE position. The damper (DEH) terminals are  
actuated any time the dehumidifier is making an internal  
blower call for air sampling or dehumidification.  
Default is MODEL 70-OFF.  
HVAC FAN – OFF/ON (SYSTEM SETUP SWITCH #2):  
The default position is WHL HOUSE.  
Determines if the HVAC fan activates during a call for  
dehumidification.  
VENT-AUTO / VENT-TIMED (SYSTEM SETUP SWITCH #4):  
Determines if ventilation is restricted based on outdoor  
temperature  
HVAC FAN-OFF position. The dehumidifier will not activate  
the HVAC fan during a call for dehumidification; it will  
however activate the HVAC fan for air cycling and ventilation.  
VENT-AUTO position. The dehumidifier will measure the  
outdoor temperature (through sensor, part # 8052) to  
determine if the ventilation damper will open. If the outside  
temperature is above 100°F or below 0°F the dehumidifier  
will not actuate the ventilation damper terminals (VENT  
DAMPER). If the outside temperature is between 0°F - 20°F,  
the dehumidifier will only actuate the ventilation damper  
terminals (VENT DAMPER) when the HVAC system is making  
a call for heat. The dehumidifier will energize the HVAC fan  
whether or not the ventilation damper opens.  
HVAC FAN-ON position. The dehumidifier will activate the  
HVAC fan during a call for dehumidification as well as for air  
cycling and ventilation.  
Default is HVAC FAN-OFF.  
VENT-TIMED position. The dehumidifier will actuate the  
ventilation damper terminals (VENT DAMPER) regardless of  
the outdoor temperature.  
The default position is VENT-AUTO.  
12  
SYSTEM CHECKOUT  
1. Check the wiring to the HVAC equipment.  
2. Rotate the main control knob clockwise to the “TEST” position.  
3. If all is set up properly, the dehumidifier blower will turn on. The compressor will turn on after the dehumidifier blower has run  
for 30 seconds. After 1 minute the dehumidifier blower and compressor will shut off (“TEST” mode only).  
4. If the dehumidifier blower does not activate in TEST mode, refer to the Troubleshooting Guide.  
®
5. For ventilation (optional) test, be sure that 24 VAC is applied in series with the Aprilaire Normally-Closed Damper  
(Model 6506) and connected to the “VENT DAMPER” terminals on the dehumidifier control.  
6. Rotate the “CYCLE TIME” potentiometer clockwise to the “TEST” position.  
7. If all is set up properly, the HVAC blower will turn on and the ventilation damper will open. Both should be audible to the  
installer. The HVAC blower will remain on and the ventilation damper will remain open for 1 minute or until the dial is turned  
from the “TEST” position, whichever happens first.  
8. If the optional ventilation damper or HVAC blower does not activate in TEST mode, refer to the Troubleshooting Guide.  
13  
TROUBLESHOOTING GUIDE  
SYMPTOM  
TROUBLESHOOTING PROCEDURE / POSSIBLE REASON  
Dehumidifier is producing  
hot air.  
• Reheat of outgoing air will cause a temperature increase across the dehumidifier.  
• Unit will possibly run continuously initially. After unit has “dried” home,  
dehumidifier will cycle, reducing load.  
Dehumidifier Blower is running,  
but no airflow.  
• Normally Open Damper was used instead of Normally Closed Damper in backflow.  
• Total HVAC system static is higher than 0.8” w.c.  
Dehumidifier not adequately  
dehumidifying.  
• Unit will need time to “dry” materials in home before effectively changing RH.  
• Too little airflow through dehumidifier.  
• Total HVAC system static is higher than 0.8” w.c.  
• Compressor is not turning on.  
• System undercharged.  
Dehumidifier is not  
draining properly.  
• Check condensate trap to be sure it is clear.  
• Check drain line for continuous slope.  
HVAC fan does not turn  
on when cycle time dial is  
in “TEST” mode.  
• Make sure there is power to the HVAC equipment.  
• Check the wiring diagram for the R, C, W, Y, GH, and GS at the HVAC equipment,  
thermostat, and the dehumidifier.  
• Make sure the sensor is connected to the Outdoor Temperature Sensor terminals  
or the System Setup block is set to “TIMED” mode.  
• Check the voltage across the R and C terminals at the dehumidifier. Voltage  
should be 18 VAC minimum - 30 VAC maximum.  
• In “TEST” Mode, the HVAC fan will activate for 1 minute, DO NOT LEAVE IN TEST  
MODE AS DEHUMIDIFIER WILL NOT OPERATE.  
The dehumidifier damper does  
not open in “TEST” Mode.  
• Follow all of the system checkout procedures.  
• Check the wiring diagram for the damper and 24 VAC transformers.  
Fan cycling operates  
continuously after the dial  
is taken off “TEST” mode.  
• If the HVAC equipment is making a Heat or Cool call, or the fan is in Continuous  
Operation, fan cycling will remain on until the requirement set by the cycle  
period dip switch and knob is met.  
• If the interval is set at 1 HOUR and the cycle time is set at 60 minutes, fan  
cycling will be on continuously. Change the setting to a lower amount if this is  
not desired.  
14  
TROUBLESHOOTING GUIDE (CONTINUED)  
SYMPTOM  
TROUBLESHOOTING PROCEDURE / POSSIBLE REASON  
The ventilation damper  
does not open when the  
HVAC fan is active.  
• The damper will not open if the cycle time within the current period has already  
been met. For instance if the cycle time is set to 5 minutes and the control has  
already ventilated for 5 minutes in that interval, the damper will remain closed.  
• If using the Outdoor Temperature Sensor, check  
that it is installed in the Outdoor Air Intake a  
maximum of 3 feet from the outside, or on the  
North, East or West side of the house.  
(Not in direct sunlight.)  
TABLE 2  
Outdoor  
Temperature  
-30˚F  
-20˚F  
-10˚F  
0˚F  
Resistance  
229,500 OHMS  
162,500 OHMS  
116,500 OHMS  
84,500 OHMS  
62,000 OHMS  
46,000 OHMS  
34,500 OHMS  
26,000 OHMS  
20,000 OHMS  
15,500 OHMS  
12,000 OHMS  
9,500 OHMS  
7,500 OHMS  
6,000 OHMS  
• If the outdoor temperature is below 0°F or above  
100°F, the damper will remain closed.  
10˚F  
20˚F  
30˚F  
40˚F  
50˚F  
60˚F  
70˚F  
80˚F  
• Verify that the Outdoor Temperature Sensor  
is reporting an accurate resistance. Remove the  
Outdoor Temperature Sensor leads from ODT  
Sensor terminals and check the resistance.  
Compare the reading with the resistance shown  
in Table 2.  
90˚F  
100˚F  
The fan turns on unexpectedly.  
The dehumidifier does not run.  
• The control will turn on the fan as needed to meet the air cycling requirements  
determined by the cycle time and cycle period settings.  
• Follow all of the system checkout procedures.  
• Check that the power switch on the dehumidifier is on.  
• Check that the circuit breaker is not tripped. The dehumidifier requires a  
minimum of 8 amps. The dehumidifier should be placed on its own dedicated  
15 amp circuit.  
The compressor never runs.  
• If a float switch is not installed, confirm that the jumper is installed at the  
float switch terminals on the control board.  
• If a float switch is installed, confirm that the float switch is not open.  
15  
DEHUMIDIFIER SEQUENCE OF OPERATION  
IF THE DEHUMIDIFIER IS NOT WIRED TO THE HVAC EQUIPMENT, THE DEHUMIDIFIER WILL SAMPLE AT THE END OF THE  
CYCLE PERIOD.  
With 3 minutes left in the Cycle Period, the dehumidifier will turn on the dehumidifier blower for 2 minutes. During this time the  
temperature and relative humidity are measured and the dewpoint is calculated. If the dewpoint is higher than the setting at the  
Control Knob then the dehumidifier compressor will turn on and the dehumidifier will run until it reaches set point.  
After reaching the set point, the dehumidifier will not sample again until the end of the next Sample Period.  
For example, if the Sample Period is set for 1 hour, the dehumidifier will sample at the end of the hour. Once the dehumidifier  
reaches set point and shuts off, the dehumidifier will not sample again until the end of the next hour.  
IF THE DEHUMIDIFIER IS WIRED INTO THE HVAC EQUIPMENT, THE DEHUMIDIFIER WILL SAMPLE THE FIRST TIME THE HVAC  
EQUIPMENT RUNS IN THE CYCLE PERIOD OR AT THE END OF THE CYCLE PERIOD IF THE HVAC EQUIPMENT DOES NOT RUN.  
For example, if the Cycle Period is set to 1 hour and the air conditioner starts 15 minutes into that hour, the dehumidifier will  
sample when the air conditioner starts. Once the dehumidifier begins dehumidifying, it will run until set point is reached. If the  
dehumidifier samples and determines that dehumidification is not needed, it will not sample again until the next Cycle Period.  
DAMPER SEQUENCE OF OPERATION  
In the Whole House Convertible to Localized installation 4 motorized dampers are used to control the air flow through the  
dehumidifier. The dampers are energized when the HVAC equipment is running. This means that when the HVAC equipment  
is running, the dampers are in the Whole-House position. When the HVAC equipment is not running, the dampers are in the  
local position.  
VENTILATION OR FAN CYCLING SEQUENCE OF OPERATION  
If the dehumidifier is providing outdoor air ventilation or fan cycling, it is monitoring the HVAC equipment to provide the amount  
of HVAC fan run time that has been set by the Cycle Time during the Cycle Period.  
If an outdoor air damper has not been installed then the dehumidifier is providing fan cycling. The dehumidifier will monitor the  
HVAC system and if the system has not run for the specified Cycle Time within the Cycle Period, the dehumidifier will energize  
the HVAC fan through the G terminal to provide the desired amount of fan run time.  
For example, if the Cycle Time is set for 10 minutes and the Cycle Period is set for 1 hour then the dehumidifier will provide  
10 minutes of fan cycling or outdoor air ventilation. If the HVAC system runs for 5 minutes during this hour then the dehumidifier  
will energize the fan for an additional 5 minutes.  
If an outdoor air damper has been installed, then the Model 1700 is providing outdoor air ventilation. The 1700 will open the  
outdoor air damper whenever the HVAC system is running, up to the amount of time specified by the Cycle Time. The  
dehumidifier will energize the HVAC fan and open the outdoor air damper to provide the desired ventilation time if the HVAC  
system has not run for the specified Cycle Time.  
If an Outdoor Temperature Sensor has been installed, then the dehumidifier will use the outdoor temperature to determine if the  
outdoor air damper is to be opened. If the outdoor temperature is above 100°F the damper will not open. If the temperature is  
between 20°F and 0°F the damper will only open with a heat call. If the outdoor temperature is below 0°F, the damper will not  
open. If the Outdoor Temperature Sensor is not installed then the temperature is not considered in opening the damper.  
10006238 5.05  
B2203431C  
P.O. BOX 1467 • MADISON, WI 53701-1467 • PHONE: 800/334-6011 • FAX: 608/257-4357 • www.aprilairecontractor.com  

Aprilaire Weather Radio 8056 User Manual
Aprilaire Thermostat B2202554C User Manual
Aprilaire Thermostat 8539 User Manual
Aprilaire Thermostat 8476 User Manual
Aprilaire Thermostat 8336 User Manual