Aprilaire Dehumidifier 60 62 User Manual

Model 60 shown.  
Automatic  
Digital Humidifier Control  
Model 60 & 62  
Safety and Installation Instructions  
READ COMPLETE INSTALLATION INSTRUCTIONS  
AND TEMPLATE BEFORE STARTING INSTALLATION.  
WARNING  
ATTENTION INSTALLER: This product must be  
installed by a qualified heating and air conditioning  
contractor. Failure to do so could result in serious  
injury from electrical shock.  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Expand Contents

INSTALLATION  
Figure B  
Use the “OFF” setting for Model 800  
Series humidifiers.  
STEP 1: Unpack the Humidifier Control Carton  
Make sure all components are present (see Figure A):  
Use Setting “A”  
A. Humidifier Control  
B. Outdoor Temperature Sensor  
C. Manual Mode Label  
for Model 400 Series  
humidifiers in areas  
with very hard water.  
The indicator will light  
after 150 hours of  
Water Panel  
Indicator  
Settings  
humidifier operation.  
A
C
Use Setting “B”  
for Model 400 Series,  
and for 500 Series, 600  
Series and 700 Series  
humidifiers in areas  
with very hard water.  
The indicator will light  
after 300 hours of  
B
Figure A  
90-1201B  
humidifier operation.  
STEP 2: Disassemble the Humidifier Control  
Use Setting “C” for Model 500 Series,  
600 Series and 700 Series humidifiers.  
The indicator will light after 600 hours of  
humidifier operation.  
Remove the knob. Remove the cover by pulling at the bottom and  
swinging it out and upward.  
90-1202B  
STEP 3: Check the Change Water Panel Indicator Setting  
This setting will control when the indicator light turns on,  
reminding you to change your water panel. If your Control came  
with a humidifier, the Control is pre-set for the humidifier. If the  
installation site has a 3-month or shorter heating season or very  
hard water, you may want to adjust the setting (see Figure B).  
The Model 62 shipped with the Model 800 Steam Humidifier is  
factory set to “OFF”. The Model 62 does not have the “Change  
Water Panel” light on the Control. The Canister Change indicator  
for the Model 800 is on the humidifier.  
4
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
DUCT (SHEET METAL) MOUNT:  
STEP 4: Determine Location for Humidifier Control  
and Mount Control  
After location for Control is selected, drill a 3/4 inch hole for the  
RH sensor (the RH sensor extends from the back of the  
Humidifier Control).  
Humidifier Control must be mounted on the Return Duct, at least  
6 inches upstream of the following (see Figure C):  
Use 2 sheet metal screws, 3/4 inch long (not provided), to mount  
the Humidifier Control. Use the mounting slot to level the Control,  
then secure the Control with the second sheet metal screw.  
• Humidifier  
• Humidifier Bypass Ductwork (if applicable)  
• Fresh Air Intake Ductwork (if applicable)  
Make sure the Humidifier Control sensor gasket is seated tightly  
around the drilled hole. Do not install Control without gasket.  
Ambient operating temperature of the Humidifier Control is to be  
from 20°F to 120°F to prevent damage to the control display.  
DUCT (FIBER BOARD) MOUNT:  
After location for Control is selected, cut a rectangular hole in  
the duct board, no smaller than 6-9/16 inches long by 4-3/8  
inches wide.  
RETURN  
DUCT  
6" MIN.  
HUMIDIFIER  
CONTROL  
Cut a rectangular piece of sheet metal to fit behind the hole in  
duct board for mounting the Humidifier Control.  
HUMIDIFIER  
Drill a 3/4 inch hole for the RH sensor (the RH sensor extends from  
the back of the Humidifier Control) into the sheet metal plate.  
COIL  
FRESH AIR  
INTAKE  
Use 2 sheet metal screws, 3/4 inch long (not provided), to mount  
the Humidifier Control.  
BYPASS  
CONNECTION  
Make sure the Humidifier Control sensor gasket is seated tightly  
around the drilled hole. Do Not Install Control Without Gasket.  
Figure C  
Secure the sheet metal plate, with the Humidifier Control  
mounted, inside the duct (see Figure D).  
90-1137  
CONTROL REPLACEMENT:  
When replacing an existing control, the duct opening left by the  
removed control must be covered completely. Locate and install  
the new control as instructed previously in Step 4.  
6
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure D – Fiber Board Duct Mount  
Figure E – Digital Humidifier Control 24V Terminals  
CONTROL BOARD  
COVER  
GASKET  
SCREW (x2)  
R
C
A
B
ODT  
W
G
H
H
Gf  
KNOB  
INSIDE OF  
RETURN  
DUCT  
OUTDOOR  
TEMPERATURE  
SENSOR  
FAN SIGNAL  
TO HVAC  
EQUIPMENT  
BASE PLATE  
SHEET METAL PLATE  
COMMUNICATION  
WITH APRILAIRE  
8570 THERMOSTAT  
HEAT SIGNAL  
FROM HVAC  
EQUIPMENT  
SOLENOID  
CONTROL  
OUTPUT  
RETURN DUCT  
RETURN  
DUCT  
SHEET METAL  
PLATE  
CUT OPENING IN  
RETURN DUCT  
24 VAC FROM  
HVAC EQUIPMENT  
“R” AND “C”  
FAN SIGNAL  
FROM  
THERMOSTAT  
90-1203B  
90-1397B  
8
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
STEP 5: Determine Location for Outdoor  
Temperature Sensor  
STEP 7: Alternate Location for Outdoor  
Temperature Sensor  
The location of the Outdoor Temperature Sensor must meet  
these three requirements:  
WARNING  
If Outdoor Temperature Sensor is mounted in an intake  
duct or pipe, do not set Blower Activation switch to “ON”.  
1. Must be mounted on North, East or West side of house out of  
direct sunlight.  
2. Must be at least 3 feet from all exhaust vents.  
The Sensor can also be mounted in the center of either:  
3. Must be above expected snow line (see Figure F).  
• PVC fresh air intake pipe for the HVAC system  
OR  
Incorrect humidity levels will result if these requirements are not  
met.  
• fresh air intake duct. Mount the sensor with a #8 galvanized  
screw.  
In both cases, the Sensor must be no more than 3 feet  
from the outside wall. See Figure G.  
Figure F  
NORTH, EAST  
OR WEST SIDE  
OF HOME  
OUTDOOR  
TEMPERATURE  
SENSOR  
If it is not feasible to use the Outdoor Temperature Sensor in any  
of the ways described, the Humidifier Control can be installed for  
Manual Operation. See “Installing the Humidifier Control for  
Manual Operation” and Figure J for details.  
SENSOR  
SENSOR  
BRACKET  
Figure G  
OUTDOOR  
TEMPERATURE SENSOR  
LEADS  
ABOVE EXPECTED  
SNOW LINE  
CENTER LINE  
90-998  
3 FEET MAX.  
STEP 6: Locate Existing Access Hole to Outside  
A convenient way to get the Sensor wire outside is to make use  
of unused wires running to the A/C condensing unit (if  
applicable). Other ways are to use existing holes for Cable TV  
lines, telephone lines, A/C lines, etc. Read all equipment  
instructions beforehand for possible conflicts and warnings.  
OUTSIDE WALL  
90-999  
10  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
When the Blower Activation switch is “ON”, the Humidifier  
Control may periodically turn the HVAC blower on to sample the  
humidity of the air.  
STEP 8: Route the Wire from Control to Sensor  
Run wire to the outdoor temperature sensor. Sensor is not  
affected by lead lengths less than 300 feet.  
Installing the Humidifier Control for  
Manual Operation  
If it is not feasible to install the Outdoor Temperature  
Sensor, the Humidifier Control can be operated in  
Manual Mode.  
CAUTION  
Do not run outdoor temperature sensor alongside  
wires carrying high voltage (120 VAC or higher).  
Secure the sensor bracket with a #8 screw.  
1. Position the Mode Switch in the “MAN” position.  
Manual indicator “M” will be displayed.  
STEP 9: Attach Sensor Wire to Humidifier Control  
Strip wire 1/4 inch, and insert the wires from the Sensor into the  
terminals labeled “ODT” on the Humidifier Control. See Figure H  
for location of terminals.  
2. Apply the Manual Mode Label to the cover,  
aligning the sticker and knob holes.  
Figure J  
Figure H  
90-1219B  
BLOWER ACTIVATION  
Set the Blower Activation Switch to “ON” to allow the Humidifier  
Control to activate the furnace fan for additional humidification.  
This may be required if the humidifier is mounted on a heat pump  
or a furnace with short run cycles.  
When the Blower Activation switch is “ON”, the Humidifier  
Control will turn on the HVAC blower when humidity is required.  
In the “OFF” position, the humidifier will only operate if humidity  
is required and the HVAC system is operating.  
90-1236B  
12  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
• Wire “Gf” on the Model 60 to “G” on the furnace terminal  
strip.  
STEP 10: Model 60 Wiring for Model 400, 500, 600 and  
700 Series Humidifiers – See Figure K  
• Wire “W” on the Model 60 to “W” on the furnace terminal  
strip.  
WARNING  
120 volts may cause serious injury from electrical  
shock. Disconnect electrical power to the furnace  
before starting installation.  
• Replace cover and knob.  
Figure K – Model 60 Wiring for Model 400, 500, 600  
and 700 Series Humidifiers  
Strip the wires used for all Humidifier Control terminal  
connections 1/4 inch.  
NOTES:  
ADHC TERMINAL STRIP  
POWER  
INPUTS  
OUTPUTS  
• The Model 60 must be continuously powered from “R” and  
“C” on the furnace to function properly.  
R
C
A
B
ODT  
W
G
H
H
Gf  
NORTH, EAST  
OR WEST SIDE  
OF HOME  
• The minimum VA required is 2.0 VA.  
OUTDOOR  
TEMPERATURE  
SENSOR FOR  
AUTOMATIC  
MODE  
• In order for the humidifier to operate, the HVAC blower must  
be running and the Model 60 must be calling for humidity.  
WIRING DESCRIPTION:  
ABOVE EXPECTED  
SNOW LINE  
• Wire external 24 VAC transformer into a constant power source  
other than the heating, ventilating, air conditioning equipment  
(HVAC) blower circuit. The transformer can be powered off the  
120 VAC line at the junction box before it enters the HVAC  
equipment. Connect the 24 volt side of the transformer to one  
of the “H” terminals on the humidifier control and to one of the  
humidifier solenoid valve wires. Connect the other solenoid  
valve wire to the other “H” terminal.  
CONNECT  
DRAIN LINE  
HERE  
CONNECT  
TO HOT WATER  
SUPPLY  
R
C
R
C
120 VAC  
G
G
Y
Y
CONTINUOUSLY POWERED  
24 VAC TRANSFORMER  
PROVIDED WITH HUMIDIFIER  
W
W
THERMOSTAT  
FURNACE  
90-1510  
• Wire “R” and “C” on the Model 60 to “R” and “C” on the  
furnace terminal strip.  
• Remove the thermostat “G” wire from the furnace terminal  
strip and wire it to “G” on the Model 60 control.  
14  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
STEP 11: Model 62 Wiring for Model 800 Series Steam  
Humidifier – See Figure L  
Figure L – Model 62 Wiring for Model 800 Series  
Steam Humidifier  
WARNING  
120/240 volts may cause serious injury from electrical  
shock. Disconnect electrical power to the furnace  
and humidifier before starting installation.  
ADHC TERMINAL STRIP  
POWER  
INPUTS  
OUTPUTS  
R
C
A
B
ODT  
W
G
H
H
Gf  
Strip the wires used for all Humidifier Control terminal  
connections 1/4 inch.  
MODEL 800  
STEAM HUMIDIFIER  
NOTES:  
OUTDOOR TEMPERATURE SENSOR  
FOR AUTOMATIC MODE  
• The Model 62 must be continuously powered from “R” and  
“C” on the furnace to function properly.  
• The minimum VA required is 2.0 VA.  
R
C
G
Y
W
R
C
G
Y
W
THERMOSTAT  
• In order for the humidifier to operate, the HVAC blower must  
be running and the Model 62 must be calling for humidity.  
WIRING DESCRIPTION:  
FURNACE  
• Wire “H” terminals on the Model 62 to the “Humidifier”  
terminals on the Model 800 control board.  
90-1511  
• Wire “R” and “C” on the Model 62 to “R” and “C” on the  
furnace terminal strip.  
• Remove the thermostat “G” wire from the furnace terminal  
strip and wire it to “G” on the Model 62 control.  
• Wire “Gf” on the Model 62 to “G” on the furnace terminal  
strip.  
• Wire “W” on the Model 62 to “W” on the furnace terminal  
strip.  
• Replace cover and knob.  
16  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Blower Activation Test  
SYSTEM CHECKOUT  
• Deactivate HVAC system or heat pump.  
• Turn knob to OFF.  
1. Replace the cover by snapping it into the Humidifier Control  
base. Also replace the knob onto the Control.  
• Set switch to Blower Activation ON.  
2. Turn Blower Activation switch to OFF  
• Turn the knob to Test/Reset. The Humidifier On light will  
illuminate. After 5 seconds, the green “Humidifier On” light  
will blink, indicating a system reset.  
3. Restore power to the HVAC system.  
4. Activate the HVAC system or heat pump (Fan or Heat).  
• If the Humidifier Control and humidifier are set up properly,  
the solenoid valve should click and the HVAC blower  
should activate.  
5. Once the blower is operating, rotate the knob of the  
Humidifier Control Clockwise to the “Test/Reset” position.  
When the knob is set in the “Test/Reset” position, the green  
“Humidifier On” light will illuminate. After 5 seconds, the  
green “Humidifier On” light will blink, indicating a system  
reset.  
• If the humidifier does not activate with the Humidifier  
Control in the “Test/Reset” position, refer to the  
troubleshooting guide.  
6. If the Humidifier Control and humidifier are set up properly,  
you should hear the solenoid valve click into the open  
position. On the Model 800 Steam Humidifier, the “Steam”  
light will illuminate green. In the “Test/Reset” position, the  
humidifier will operate for 1 minute. If the Humidifier Control  
is left in the “Test/Reset” position for more than 1 minute,  
the “H” terminals will open (closing the solenoid valve), and  
the knob and display backlights will flash, indicating that the  
Humidifier Control is still in the “Test/Reset” position.  
• If HVAC blower does not activate with the Humidifier  
Control in the "Test/Reset" position, refer to the  
troubleshooting guide.  
8. Setting the Humidifier Control:  
• If the home is occupied, set the Humidifier Control to  
“Normal”. (For Manual Mode, set to 35%.)  
• If the home is vacant, set the Humidifier Control to “OFF”.  
• If in Manual Mode and system is installed during cooling  
season, set the Humidifier Control to “OFF”.  
7. If the humidifier does not activate with the Humidifier Control  
in the “Test/Reset” position, refer to the troubleshooting  
guide.  
9. Instruct the homeowner to refer to the Aprilaire Owner’s  
Manual for the initial adjustment period.  
10. Make sure the red “Call Dealer for Service” light is not  
flashing. If the red “Call Dealer for Service” light is flashing,  
refer to the troubleshooting guide.  
18  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TROUBLESHOOTING PROCEDURE (CONTINUED)  
TROUBLESHOOTING GUIDE  
3. Rotate Humidifier Control knob to the “Test/Reset” position.  
After 5 seconds, the green “Humidifier On” light will blink,  
resetting the error. If E3 returns, replace the Humidifier  
Control.  
SYMPTOM  
Call Dealer For Service Light Flashing (see Figure M).  
TROUBLESHOOTING PROCEDURE  
Manual Mode (switch in “MAN” position)  
Applies to both Automatic and Manual Operation unless  
indicated otherwise.  
1. Make sure the ODT terminals are clear of any wires that  
may short the terminals together other than the ODT sensor.  
Display Error Code: E1: RH Sensor  
2. Rotate Humidifier Control knob to the “Test/Reset” position.  
After 5 seconds, the green “Humidifier On” light will blink,  
resetting the error. If E3 returns, replace the Humidifier  
Control.  
Rotate Humidifier Control knob to the “Test/Reset” position.  
After 5 seconds, the green “Humidifier On” light will blink,  
resetting the error. If E1 returns, replace the Humidifier Control.  
Display Error Code: E4: Communication  
Display Error Code: E2: Control Knob  
This error applies to systems wired to an Aprilaire Model 8570  
Thermostat (see Figure Q) using the “A” and “B” terminals.  
Rotate the Humidifier Control knob to the “Test/Reset”  
position. After 5 seconds, the green “Humidifier On” light will  
blink, resetting the error. If E4 returns, check the wiring  
between the Digital Humidifier Control and Model 8570 check  
the connections at “A”and “B” on the humidifier control and  
the Model 8570. Make sure the Model 8570 is wired and  
operating properly according to the Model 8570 manual.  
Rotate Humidifier Control knob to the “Test/Reset” position.  
After 5 seconds, the green “Humidifier On” light will blink,  
resetting the error. If E2 returns, replace the Humidifier Control.  
Display Error Code: E3: Outdoor Temperature Sensor  
Auto Mode (switch in “AUTO” position)  
1. Make sure that the Outdoor Temperature Sensor is properly  
connected to the ODT terminals on the Humidifier Control.  
2. Measure the resistance of the Outdoor Temperature Sensor  
by removing the leads from the Humidifier Control terminals  
and measuring the resistance across the wires with an  
ohmmeter. Confirm the reading with the temperature in  
Table 1 on page 22. Reconnect the ODT Sensor leads. If the  
resistance value does not match the temperature value,  
replace the Outdoor Temperature Sensor.  
20  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TABLE 1  
SYMPTOM  
Outdoor Temperature (°F) Resistance (k) 10  
Humidifier does not operate in “Test/Reset” mode.  
-30  
-20  
-10  
0
231.8  
163.4  
117.3  
84.8  
62.2  
46.1  
34.4  
26.1  
19.9  
15.3  
11.9  
9.3  
TROUBLESHOOTING PROCEDURE  
• Check wiring diagrams for correct Humidifier Control  
installation  
10  
20  
30  
40  
50  
60  
70  
80  
90  
100  
• Make sure that the blower is operating and the HVAC  
system is calling for heat.  
• Check wiring diagrams for correct Humidifier Control  
installation.  
• If connected to a Model 400 Series humidifier, make sure  
both floats in the bottom of the scale control insert are in  
the down position. If necessary, dump out water to lower  
the floats.  
7.3  
5.8  
Figure M  
• Check voltage at the Humidifier Control “R” and “C”  
terminals. Voltage should be 22 VAC minimum to 30 VAC  
maximum.  
Red “Call Dealer For Service” Light  
Yellow “Change Water Panel” Light  
Green “Humidifier On” Light  
• Make sure that the saddle valve is open.  
• In “Test/Reset mode, the humidifier will operate for 1  
minute only. DO NOT LEAVE THE HUMIDIFIER CONTROL IN  
“TEST/RESET” MODE AS THE HUMIDIFIER WILL NOT  
OPERATE.  
90-1227  
22  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SYMPTOM  
SYMPTOM  
Humidifier operates only in “Test/Reset” mode.  
Yellow “Change Water Panel” light is blinking (see Figure M).  
• If outdoor temperature is greater than 60°F or less than  
-30°F, the Humidifier Control will only operate in the  
“Test/Reset” mode (for 1 minute).  
TROUBLESHOOTING PROCEDURE  
Check the condition of the Water Panel and replace it if  
mineral deposits are blocking air flow. Follow the instructions  
on the Water Panel box. Rotate the knob to the “Test/Reset”  
position for at least 5 seconds to reset Water Panel change  
timer. Check that the timer setting is correct for the humidifier  
model and water conditions (see Figure B). DO NOT LEAVE  
THE HUMIDIFIER CONTROL IN “TEST/RESET” MODE AS THE  
HUMIDIFIER WILL NOT OPERATE.  
• If the humidity level in the home is higher than the  
Humidifier Control knob setting, the Humidifier Control will  
not operate the humidifier.  
TROUBLESHOOTING PROCEDURE  
• Measure the resistance of the Outdoor Temperature Sensor  
by removing the leads from the Humidifier Control terminals  
and measuring the resistance across the wires with an  
ohmmeter. Confirm the reading with the temperature in  
Table 1. Reconnect the ODT Sensor leads. If the resistance  
value does not match the temperature value, replace the  
Outdoor Temperature Sensor.  
• Make sure that the Outdoor Temperature Sensor is mounted  
completely outside the house on the North, East or West  
side of the house and out of direct sunlight. (Automatic  
Mode Only)  
• Make sure that the Outdoor Temperature Sensor is located  
at least 3 feet away from all exhaust vents. (Automatic  
Mode Only)  
• If Outdoor Temperature Sensor is mounted in the fresh air  
intake duct, make sure that the sensor is no more than 3  
feet from the outside wall. (Automatic Mode Only)  
24  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SYMPTOM  
SYMPTOM  
Humidifier operates constantly.  
Humidifier or Humidifier Control “chatters” or clicks On and  
Off rapidly.  
• If the humidity level in the home is less than the Humidifier  
Control knob setting and there is a continuous fan call or  
heat call (depending on setup), the Humidifier Control will  
operate the humidifier until the humidity level is higher than  
the Humidifier Control knob setting.  
TROUBLESHOOTING PROCEDURE  
• Check for steady 22 VAC to 30 VAC across the “R” and “C”  
terminals of the Humidifier Control with a voltmeter.  
• Check, with a voltmeter, that the HVAC signal across the  
“W” and “C” and “G and C” terminals of the Humidifier  
Control is a steady 22 VAC to 30 VAC.  
TROUBLESHOOTING PROCEDURE  
• Set Blower Activation switch to OFF.  
• Make sure that the Outdoor Temperature Sensor wiring is  
not running alongside other wires carrying high voltage  
(120 VAC or higher). (Automatic Mode Only)  
• In the “Test/Reset” mode, verify that the humidifier turns off  
after 1 minute.  
• Check the Outdoor Temperature Sensor resistance and  
location, as instructed on the previous page.  
• Rotate the Humidifier Control knob counterclockwise to the  
“Off” position, and observe whether the humidifier turns  
off. If the humidifier still operates in the “Off” position,  
perform the following:  
SYMPTOM  
Humidifier blower does not activate during Blower Activation  
Test.  
1. Check the wiring diagram for correct Humidifier Control  
Installation.  
TROUBLESHOOTING PROCEDURE  
• Set the Blower Activation Switch to “ON”.  
2. Remove the wires from the “H” terminals on the  
Humidifier Control. If the humidifier continues to operate,  
replace the solenoid valve.  
• Check wiring diagrams for correct Humidifier Control  
installation.  
26  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
RESEARCH PRODUCTS CORPORATION  
P.O. BOX 1467 • MADISON,WI 53701-1467  
Call 800/334-6011 • FAX 608/257-4357  
10008977 6.10  
B2205119A  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Aprilaire Thermostat 8476 User Manual
Aprilaire Humidifier 350 User Manual
Aprilaire Freezer Freezer PLUS Series User Manual
Aprilaire Dehumidifier 1750A 1770A User Manual
Aprilaire Appliance Trim Kit 6404 User Manual