Aprilaire Thermostat 61000652C 8400 Tstat User Manual

8400 Series Thermostats  
Safety &  
Installation  
Instructions  
READ AND SAVE THESE INSTRUCTIONS  
Download from Www.Somanuals.com. All Manuals Search And Download.  
61000652C 8400 Tstat Install.indd  
1
10/13/09 11:08:56 AM  

Expand Contents

INSTAllATION  
INSTAllATION lOCATION RECOmmENDATIONS  
Thermostat should be mounted:  
Do not mount thermostat:  
• On an interior wall, in a frequently occupied space.  
• Approximately 5‘ above floor.  
• Behind doors, in corners, or other dead air spaces.  
• In direct sunlight, near lighting fixtures, or other  
appliances that give off heat.  
• At least 18” from outside wall.  
• On an outside or unconditioned area wall.  
• Thermostat can be mounted to a vertical junction box.  
• In the flow of a supply register, in stairwells, or near  
outside doors.  
• On a wall with concealed pipes or ductwork.  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
61000652C 8400 Tstat Install.indd  
3
10/13/09 11:08:57 AM  
INSTAllATION  
OUTDOOR TEmpERATURE SENSOR (OpTIONAl)  
Outdoor temperature can be measured by attaching an  
8052 sensor to the S1 and S2 terminals. System setting  
#05 (Remote sensor) is used to enable sensor.  
• Install on side of building out of direct sunlight  
(north side recommended).  
• Mount above snow line.  
Heat pump models can use the outdoor temperature to  
effectively utilize the heat pump:  
• Mount at least 3’ away from exhaust vents and  
condensing lines.  
• When the outdoor temperature is less than the Low  
Balance Point, the heat pump will be locked out and  
only auxiliary heating will be used.  
• Maximum wire length is 300’.  
• Do not route wires along 120 VAC lines.  
• When the outdoor temperature is higher than the High  
Balance Point, the auxiliary heating will be locked out  
and only the heat pump will be used to provide heating.  
RC  
R
W
Y
G
C
S1 S2 O/B  
L
W2 Y2  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
61000652C 8400 Tstat Install.indd  
4
10/13/09 11:08:57 AM  
INSTAllATION  
THERmOSTAT mOUNTINg  
pOwER & RESET OpTIONS  
The thermostat is dual power. It can either be AC or  
battery powered, or both (to provide backup power for  
the clock). Batteries are optional if the thermostat was  
connected to AC power when installed.  
For heat pump models (8446, 8448HP, 8465, 8466HP)  
24 VAC must be connected in order for the system fault  
and emergency heat indicators to operate.  
The thermostat has a memory backup that saves the  
thermostat’s settings in case of a power interruption.  
The reset button located under the battery cover can be  
used to reset the thermostat back to factory defaults.  
The system settings will also be reset back to defaults.  
1. Remove the back of the thermostat, by pressing the  
tab on the bottom of the unit.  
2. Pull wires through the opening on the back of the  
thermostat.  
3. Position and level the back of the thermostat on wall  
and mark the hole locations with a pencil.  
4. Drill 1/4” holes & insert supplied anchors (drywall only).  
5. Place back over anchors, insert and tighten screws.  
6. Seal wire entry holes to prevent drafts affecting  
temperature readings.  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
61000652C 8400 Tstat Install.indd  
5
10/13/09 11:08:58 AM  
INSTAllATION  
wIRINg TERmINAl  
wire specifications  
RC – 24 VAC supply cooling*  
R – 24 VAC supply heating*  
18-24 gauge thermostat wire  
w – 1st stage heat / auxiliary  
Y – 1st stage cooling / compressor  
g – Fan  
Installation notes  
• Ensure power at the HVAC equipment is off.  
C – Common (optional when powered by batteries)  
S1 & S2 – outdoor temperature sensor (optional)  
O/b – Reversing valve  
• Loosen screw terminals, insert stripped wire and  
re-tighten.  
• Push the excess wire back into the opening and plug  
the wall opening to prevent drafts.  
l – System fault indicator  
w2 – 2nd stage heat / auxiliary  
Y2 – 2nd stage cooling / compressor  
*Jumper between RC & R is used in single transformer systems  
(see wiring diagrams).  
RC  
R
W
Y
G
C
S1 S2 O/B  
L
W2 Y2  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
61000652C 8400 Tstat Install.indd  
6
10/13/09 11:08:58 AM  
INSTAllATION  
wIRINg – mODEl 8463 & 8444 SINglE  
TRANSfORmER (USE jUmpER wIRE)  
wIRINg – mODEl 8463 & 8444 TwO  
TRANSfORmERS (REmOVE jUmpER wIRE)  
RC  
R
W
Y
G
C
S1 S2  
RC  
R
W
Y
G
C
S1 S2  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
61000652C 8400 Tstat Install.indd  
7
10/13/09 11:08:58 AM  
INSTAllATION  
wIRINg – mODEl 8465 & 8446 SINglE  
TRANSfORmER (USE jUmpER wIRE)  
wIRINg – mODEl 8465 & 8446 TwO  
TRANSfORmERS (REmOVE jUmpER wIRE)  
RC  
R
W
Y
G
C
S1 S2 O/B  
L
RC  
R
W
Y
G
C
S1 S2 O/B  
L
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
61000652C 8400 Tstat Install.indd  
8
10/13/09 11:08:58 AM  
INSTAllATION  
wIRINg – mODEl 8466 & 8448 SINglE  
TRANSfORmER (USE jUmpER wIRE)  
fOR HEAT/COOl SYSTEm  
wIRINg – mODEl 8466 & 8448 TwO  
TRANSfORmERS (REmOVE jUmpER wIRE)  
fOR HEAT/COOl SYSTEm  
RC  
R
W
Y
G
C
S1 S2 O/B  
L
W2 Y2  
RC  
R
W
Y
G
C
S1 S2 O/B  
L
W2 Y2  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
61000652C 8400 Tstat Install.indd  
9
10/13/09 11:08:58 AM  
INSTAllATION  
wIRINg – mODEl 8466 & 8448 SINglE  
TRANSfORmER (USE jUmpER wIRE)  
fOR HEAT pUmp SYSTEm  
wIRINg – mODEl 8466 & 8448 TwO  
TRANSfORmERS (REmOVE jUmpER wIRE)  
fOR HEAT pUmp SYSTEm  
RC  
R
W
Y
G
C
S1 S2 O/B  
L
W2 Y2  
RC  
R
W
Y
G
C
S1 S2 O/B  
L
W2 Y2  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
61000652C 8400 Tstat Install.indd 10  
10/13/09 11:08:59 AM  
SETUp & TESTINg  
SYSTEm SETUp INSTRUCTIONS  
The following instructions show how to enter the system setup menu and change settings. The table on the  
following pages lists the settings and their details. Default settings are shown in bold. Some settings are only  
available to certain models, and some are specific to thermostats set to heat pump mode.  
How to enter the system setup menu to change  
system settings  
press  
press  
or  
to change the setting.  
to change to the next option.  
press  
repeatedly until system is set to OFF.  
press  
displayed.  
after the last setting. “DONE” will be  
press and hold  
and  
for three seconds.  
The screen of the first setting will be displayed.  
The thermostat will return to Normal mode if no key is  
pressed in 3 seconds.  
To reset all system settings back to default, press the  
RESET button located under the battery door.  
SETTING VALUE  
SYSTEM SETTING NUMBER  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
61000652C 8400 Tstat Install.indd 11  
10/13/09 11:08:59 AM  
SETUp & TESTINg  
SYSTEm SETUp INSTRUCTIONS (CONTINUED)  
Thermostat models 8448 & 8466 have the option of being used in heat pump or heat/cool systems. Switch SW1  
located on the back of the thermostat’s face is used to select this. System setting number 00 will only be shown on  
these models to display the position of SW1.  
Sw1  
HEAT PUMP  
HEAT/COOL  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
61000652C 8400 Tstat Install.indd 12  
10/13/09 11:08:59 AM  
SETUp & TESTINg  
SYSTEm SETUp INSTRUCTIONS (CONTINUED)  
System setting  
Setting range, default in bold  
0 : heat/cool  
1 : heat pump  
00 Equipment type (8466, 8448) (Set by Sw1)  
0 : fahrenheit  
1 : Celsius  
01 Temperature scale  
0 : gas or oil furnace (Equipment controls fan)  
1 : Electric (Thermostat controls fan)  
02 Fan control in heating  
0° : No offset applied  
–4°F to +4°F (–2°C to +2°C)  
03 Offset temperature for internal sensor  
04 Auto mode  
0 : Auto mode is disabled  
1 : Auto mode is enabled  
0 : No outdoor temperature sensor attached  
1 : Outdoor temperature sensor attached  
05 Outdoor temperature sensor  
06 Compressor minimum off time  
07 Heating minimum off time  
08 Equipment minimum on time  
5 minutes  
1 to 5 minutes in 1 minute steps  
2 minutes  
1 to 5 minutes  
2 minutes  
1 to 5 minutes  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
61000652C 8400 Tstat Install.indd 13  
10/13/09 11:08:59 AM  
SETUp & TESTINg  
SYSTEm SETUp INSTRUCTIONS (CONTINUED)  
System setting  
Setting range, default in bold  
1°f (0.5°C)  
1°F to 4°F (0.5°C to 2°C)  
09 1st stage differential  
1°f (0.5°C)  
1°F to 4°F (0.5°C to 2°C)  
10 2nd stage differential (8448, 8466)  
1°f (0.5°C)  
1°F to 4°F (0.5°C to 2°C)  
11 3rd stage differential (8448HP, 8466HP)  
12 Reverse valve (8446, 8466HP, 8465, 8466HP)  
0 – O/b energized in cooling (O)  
1 – O/B energized in heating (B)  
13 Integral factor period (P+I control)*  
4 minutes  
1 to 5 minutes or “OFF” to disable  
Set to OFF for proportional control only  
3°f (2°C)  
2°F to 5°F (1°C to 3°C)  
14 Deadband (auto mode)  
0 : Progressive recovery is disabled  
1 : progressive recovery is enabled  
15 Progressive recovery (8463, 8465, 8466)  
*The integral factor is used in the equipment control algorithm to maintain the space temperature at set point.  
A short integral factor period will increase the number of cycles per hour. (A short integral factor period will be more  
comfortable.) A long integral factor period will lower the number of cycles per hour. (A long integral factor period will  
be more economical.)  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
61000652C 8400 Tstat Install.indd 14  
10/13/09 11:09:00 AM  
SETUp & TESTINg  
SYSTEm SETUp INSTRUCTIONS (CONTINUED)  
System setting  
Setting range, default in bold  
16 Low Balance Pt. (8446, 8448HP, 8465, 8466HP)  
20°f (–7°C)  
1°F to 35°F (–17°C to 1°C) or “OFF” to disable  
System setting 05 must be enabled  
17 High Balance Pt. (8446, 8448HP, 8465, 8466HP)  
60°f (16°C)  
40°F to 80°F (4°C to 27°C) or “OFF “ to disable  
System setting 05 must be enabled  
0 – 5/2 program (weekdays and weekends)  
1 – 5/1/1 program (Weekdays, Sat. and Sun.)  
19 Program format (8463, 8465, 8466)  
20 Change air filter  
Off  
1, 3, 6, 12 months or “OFF” to disable  
21 Change water panel**  
Off  
Set number of months until reminder is required  
1 to 12 months or “OFF” to disable  
0 : flow through type humidifier (1 reminder per season)  
1 : Drain-less type humidifier (2 reminders per season)  
22 Humidifier type**  
23 Service dehumidifier  
24 Service HVAC  
Off  
1 to 12 months or “OFF” to disable  
Off  
1 to 12 months or “OFF” to disable  
**If humidifier type is set to Drain-less, then the first reminder is based on the system setting 21, second reminder  
will activate 3 months later. If humidifier type is set to Flow through, then the first reminder is based on system  
setting 21, second reminder will activate 12 months later.  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
61000652C 8400 Tstat Install.indd 15  
10/13/09 11:09:00 AM  
SETUp & TESTINg  
SYSTEm TEST mODE  
The system test mode is used to test a system after installation. The outputs of the thermostat can be manually  
activated one at a time to test their function. The following instructions show how to enter the test mode and turn  
outputs on and off. The charts on the following pages show all of the options for each model.  
The test steps are:  
Test  
Number  
Heat/Cool models  
8444, 8463, 8448HC, 8466HC  
Heat pump models  
8446, 8465, 8448Hp, 8466Hp  
50  
51  
52  
53  
Heating (W) (W2)  
Cooling (Y) (Y2)  
Fan (G)  
Aux Heating (W) (W2)  
Compressor Cooling (Y) (Y2)  
Compressor Heating (Y) (Y2)  
Fan (G)  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
61000652C 8400 Tstat Install.indd 16  
10/13/09 11:09:00 AM  
SETUp & TESTINg  
SYSTEm TEST mODE (CONTINUED)  
How to enter the system test menu  
press  
output, press  
to turn on the output (01). For multi stage  
again to turn on the 2nd stage (02).  
press  
repeatedly until system is set to OFF.  
press  
press  
to turn off the output (00).  
press and hold  
and  
for three seconds.  
to change to the next test step.  
after the last test step. “DONE” will be  
The screen of the first test step #50 is displayed:  
press  
displayed.  
The thermostat will return to Normal mode if no key is  
pressed in 3 seconds.  
FLASHES IF 24VAC  
IS NOT PRESENT  
SYSTEM TEST  
NUMBER  
MODE (SW1 SETTING  
8448 & 8466 ONLY)  
OUTPUT STATUS  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
61000652C 8400 Tstat Install.indd 17  
10/13/09 11:09:00 AM  
SETUp & TESTINg  
Test steps for 8444 & 8463  
System Setting  
Display (Output)  
01  
01  
01  
fAN ON  
(g)  
Step  
Key Input  
#2  
HEATINg  
ON (w)  
COOlINg  
ON (Y)  
0 : Gas  
1 : Elec  
ON  
ON  
[UP]  
#50 Heat  
ON  
ON  
ON  
[DOWN]  
[UP]  
ON  
#51 Cool  
[DOWN]  
[UP]  
#52 Fan  
[DOWN]  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
61000652C 8400 Tstat Install.indd 18  
10/13/09 11:09:01 AM  
SETUp & TESTINg  
Test steps for 8448HC & 8466HC  
System Setting  
Display (Output)  
01  
02  
01  
02  
01  
fAN ON  
(g)  
Step  
Key Input  
#2  
HEATINg  
ON (w)  
HEATINg  
ON (w2)  
COOlINg  
ON (Y)  
COOlINg  
ON (Y2)  
0 : Gas  
1 : Elec  
0 : Gas  
1 : Elec  
ON  
ON  
ON  
ON  
1st [UP]  
2nd [UP]  
ON  
ON  
#50 Heat  
ON  
ON  
[DOWN]  
1st [UP]  
2nd [UP]  
[DOWN]  
[UP]  
ON  
ON  
ON  
ON  
#51 Cool  
ON  
ON  
#52 Fan  
[DOWN]  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
61000652C 8400 Tstat Install.indd 19  
10/13/09 11:09:01 AM  
SETUp & TESTINg  
Test steps for 8446 & 8465  
System Setting  
Display (Output)  
01 AUX  
HEATINg  
ON (w)  
01  
01  
fAN ON  
(g)  
Step  
Key Input  
#2  
#12  
COOl/HEAT  
ON (Y)  
O/b  
0 : Gas  
1 : Elec  
ON  
ON  
[UP]  
[DOWN]  
[UP]  
#50 Aux  
ON  
0 : O  
1 : B  
0 : O  
1 : B  
0 : O  
1 : B  
0 : O  
1 : B  
ON  
ON  
ON  
ON  
ON  
ON  
#51 Cool  
[DOWN]  
[UP]  
ON  
ON  
ON  
ON  
ON  
ON  
#52 Heat  
#53 Fan  
[DOWN]  
[UP]  
ON  
[DOWN]  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
61000652C 8400 Tstat Install.indd 20  
10/13/09 11:09:01 AM  
SETUp & TESTINg  
Test steps for 8448Hp & 8466Hp  
System Setting  
Display (Output)  
01 AUX  
HEATINg  
ON (w)  
ON  
ON  
ON  
ON  
02 AUX  
01  
02  
01  
Step  
Key Input  
#2  
#12  
HEATINg COOl/HEAT COOl/HEAT fAN ON  
O/b  
ON (w2)  
ON (Y)  
ON (Y2)  
(g)  
ON  
ON  
0 : Gas  
1 : Elec  
0 : Gas  
1 : Elec  
1st [UP]  
#50 Aux  
ON  
ON  
2nd [UP]  
[DOWN]  
1st [UP]  
0 : O  
1 : B  
0 : O  
1 : B  
0 : O  
1 : B  
0 : O  
1 : B  
0 : O  
1 : B  
0 : O  
1 : B  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
#51 Cool  
2nd [UP]  
[DOWN]  
1st [UP]  
2nd [UP]  
[DOWN]  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
#52 Heat  
#53 Fan  
[UP]  
ON  
[DOWN]  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
61000652C 8400 Tstat Install.indd 21  
10/13/09 11:09:02 AM  
QUICK REfERENCE TO CONTROlS & DISplAY  
NON-pROgRAmmAblE mODElS (8444, 8446, 8448)  
CURRENT INDOOR TEMPERATURE  
OUTDOOR TEMPERATURE (OPTIONAL)  
TEMPERATURE SETTING  
SYSTEM MODE  
SETTING  
EQUIPMENT STATUS  
SYSTEM MODE  
FAN SETTING  
UP  
DOWN  
HEAT pUmp mODElS ONlY  
EMERGENCY HEAT (RED)  
SYSTEM FAULT (YELLOW)  
FAN SETTING  
INDICATOR SHOWS THROUGH HOUSING  
QUICK REFERENCE CARD  
BATTERY DOOR  
MESSAGE CENTER  
LOW BATTERY WARNING  
NOTE: BACKLIGHT IS ACTIVATED WITH FIRST BUTTON PRESS AND AUTOMATICALLY TURNS OFF.  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
61000652C 8400 Tstat Install.indd 22  
10/13/09 11:09:02 AM  
QUICK REfERENCE TO CONTROlS & DISplAY  
pROgRAmmAblE mODElS (8463, 8465, 8466)  
CURRENT INDOOR TEMPERATURE  
CURRENT TIME  
OUTDOOR TEMPERATURE (OPTIONAL)  
TEMPERATURE SETTING  
SYSTEM MODE  
SETTING  
EQUIPMENT STATUS  
UP  
FAN SETTING  
SYSTEM MODE  
FAN SETTING  
PROGRAM  
DOWN  
HOLD  
HEAT pUmp mODElS ONlY  
EMERGENCY HEAT (RED)  
SYSTEM FAULT (YELLOW)  
CURRENT  
SCHEDULE  
PERIOD  
INDICATOR SHOWS THROUGH HOUSING  
QUICK REFERENCE CARD  
BATTERY DOOR  
MESSAGE CENTER  
LOW BATTERY WARNING  
NOTE: BACKLIGHT IS ACTIVATED WITH FIRST BUTTON PRESS AND AUTOMATICALLY TURNS OFF.  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
61000652C 8400 Tstat Install.indd 23  
10/13/09 11:09:02 AM  
THERmOSTAT fEATURES  
All 8400 SERIES THERmOSTATS  
pROgRAmmAblE mODElS ONlY  
(8463, 8465, 8466)  
• Large, clear, backlit display is easy to read – even  
• Separately programmable weekday/weekend  
in the dark.  
schedules.  
• Displays room temperature, temperature setting, and  
• Easy to use temperature control can override  
optional outdoor temperature.  
program schedule at any time.  
• Dual power option (Battery or 24 VAC).  
• Front battery door access for fast, easy replacement.  
• Built in compressor protection.  
• Progressive recovery. Progressive Recovery feature  
allows the thermostat to activate the heating and  
cooling equipment prior to an event in order to reach  
the desired temperature at the start of the next  
scheduled event.  
• Circulation fan mode for air cleaning.  
• Water panel, dehumidifier, air filter, and HVAC  
service indicators.  
• System test mode.  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
61000652C 8400 Tstat Install.indd 24  
10/13/09 11:09:02 AM  
TROUblESHOOTINg  
DISplAY IS blANK  
HEATINg SYSTEm DOES NOT RESpOND  
(“HEATINg” AppEARS ON SCREEN)  
• Check circuit breaker and reset if necessary.  
• Check for 24 VAC at the equipment on the secondary  
side of the transformer between power and  
common. If voltage is not present, check the heating  
equipment to find the cause of the problem.  
• Make sure power switch at heating & cooling  
system is on.  
• Make sure furnace door is closed securely.  
• If thermostat is battery powered, make sure fresh AA  
alkaline batteries are correctly installed.  
• Check for 24 VAC between the heat terminal (W)  
and the transformer common. If 24 VAC is present,  
the thermostat is functional. Check the heating  
equipment to find the cause of the problem.  
TEmpERATURE SETTINgS DO NOT CHANgE  
• Check for loose or broken wires between the  
thermostat and the heating equipment.  
Make sure heating and cooling temperatures are set to  
acceptable ranges:  
Heat: 45° to 90°F (7° to 32°C).  
Cool: 50° to 99°F (10° to 37°C).  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
61000652C 8400 Tstat Install.indd 25  
10/13/09 11:09:03 AM  
TROUblESHOOTINg  
COOlINg SYSTEm DOES NOT RESpOND  
HEAT/COOl bOTH ON AT SAmE TImE  
(“COOlINg” AppEARS ON SCREEN)  
• Check SW1 (Equipment Type), to make sure it is set  
to match the installed heating/cooling equipment  
(see page 12).  
• Check for 24 VAC at the equipment on the secondary  
side of the transformer between power and  
common. If voltage is not present, check the cooling  
equipment to find the cause of the problem.  
• Check to make sure heating and cooling wires are  
not shorted together.  
• Check for 24 VAC between the cooling terminal (Y)  
and the transformer common. If 24 VAC is present,  
the thermostat is functional. Check the cooling  
system to find the cause of the problem.  
HEATINg EQUIpmENT IS RUNNINg IN  
COOl mODE  
• Check SW1 (Equipment Type), to make sure it is set  
to match the installed heating/cooling equipment  
(see page 12).  
• Check for loose or broken wires between the  
thermostat and the cooling equipment.  
fAN DOES NOT TURN ON IN A CAll fOR HEAT  
“HEATINg” IS NOT DISplAYED  
• Check System Setting #02 (Fan Control), to make  
sure the fan control is properly set to match the type  
of system (see page 11).  
• Change the System Mode to Heat, and set  
the temperature level above the current room  
temperature.  
HEAT pUmp ISSUES COOl AIR IN HEAT mODE,  
OR wARm AIR IN COOl mODE  
“COOlINg” IS NOT DISplAYED  
• Change the System Mode to Cool, and set  
the temperature level below the current room  
temperature.  
• Check System Setting #12 (Reversing Valve), to make  
sure it is properly configured for your system (see  
page 11).  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
61000652C 8400 Tstat Install.indd 26  
10/13/09 11:09:03 AM  
SpECIfICATIONS  
Environment  
Operating: 32° to 120°F (0° to 48.9°C)  
Shipping: -30° to 140°F (-34.4° to 60°C)  
Temperature  
Relative humidity  
Operating: 5% to 90% R.H. (non-condensing)  
Electrical  
Operating voltage  
Current  
24 VAC (18 – 30 VAC)  
Maximum: 2.5A (total), 1.0A (single output)  
Maximum surge current: 5A  
Dual power. Can be battery or 24 VAC powered.  
Power supply  
When both the sources are available, battery will be used as  
back up power.  
Battery power: AA size alkaline battery x 2  
Battery life: Approximately 1 year  
Battery power  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
61000652C 8400 Tstat Install.indd 27  
10/13/09 11:09:03 AM  
SpECIfICATIONS  
Thermal  
Outdoor temperature sensor  
Maximum distance: 300 feet  
Display range: 32° to 99°F (0° to 40°C)  
Display range: -20° to 130°F (-30° to 55°C)  
Room temperature measurement  
Outdoor temperature measurement  
Heat: 45° to 90°F (7° to 32°C)  
Cool: 50° to 99°F (10° to 37°C)  
Temperature setting range  
RESEARCH PRODUCTS CORPORATION  
P.O. BOX 1467 • MADISON, WI 53701-1467 • www.aprilaire.com  
61000652 10.09  
B2204777C  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
61000652C 8400 Tstat Install.indd 28  
10/13/09 11:09:03 AM  