Aprilaire Thermostat 8800 UNIVERSAL User Manual

Model 8800 Universal  
Communicating Thermostat  
Owners Manual  
Includes  
Operating Instructions and  
Warranty Information  
READ AND SAVE THESE INSTRUCTIONS  
Download from Www.Somanuals.com. All Manuals Search And Download.  
61000762A 8800 Tstat Owners.indd  
1
3/28/11 4:19:57 PM  

Expand Contents

AbOUT yOUR NEw THERMOSTAT  
wARNING  
Do not use sharp instruments to press touch screen. Only use your fingertips.  
THERMOSTAT fEATURES  
• Large touch screen with adjustable backlight – constant backlight available.  
• Message center provides feedback and instructions.  
• 7 day programmability or separately programmable weekday/weekend schedules.  
• Thermostat can be removed from the wall for easy programming (batteries must be installed).  
• Front battery door access for fast, easy replacement.  
• Displays room temperature, room humidity, temperature setting, and optional outdoor temperature.  
• Air filter, humidifier, dehumidifier, and HVAC service indicators.  
• Programmable fan control with fan circulation mode.  
• Easy to use temperature control can override program schedule at any time.  
• Progressive recovery ensures proper temperature at the start of a program event.  
• Built in compressor protection prevents damage to your equipment.  
• RS485 communications ready.  
• Universal system compatibility.  
• Configurable to control a humidifier and dehumidifier.  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
61000762A 8800 Tstat Owners.indd  
3
3/28/11 4:19:57 PM  
AbOUT yOUR NEw THERMOSTAT  
CONTROlS & DISplAy OVERVIEw – HOME SCREEN  
ROOM TEMPERATURE  
CURREnT DAy oUTDooR TEMPERATURE  
TEMPERATURE SETTING  
RooM RELATiVE HUMiDiTy  
FAn MoDE  
BUTTON  
TEMPERATURE  
ADJUSTMEnT  
FAn MoDE  
SETTING  
HoLD BUTTon  
(in PRogRAMMABLE MoDE  
SETS oR CLEARS HoLD)  
SySTEM MoDE  
BUTTON  
nETwoRk oVERRiDE  
(in non-PRogRAMMABLE MoDE)  
SySTEM MoDE  
SETTING  
HEAT pUMp MODE ONly  
EMERgEnCy/AUXiLiARy  
EQUIPMENT  
STATUS  
HEAT (RED)  
SySTEM FAULT (yELLow)  
inDiCAToR SHowS THRoUgH HoUSing  
MESSAGE  
CENTER  
(SCRoLLing TEXT)  
Low BATTERy  
inDiCAToR  
CURREnT TiME & DATE  
MAIN MENU BUTTON  
NOTE: BACkLigHT iS ACTiVATED wiTH FiRST BUTTon PRESS AnD AUToMATiCALLy TURnS oFF.  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
61000762A 8800 Tstat Owners.indd  
4
3/28/11 4:19:59 PM  
AbOUT yOUR NEw THERMOSTAT  
CONTROlS & DISplAy OVERVIEw – MAIN MENU  
CLEAN SCREEN  
(LOCKOUT TOUCH SCREEN  
FoR 30 SEConDS)  
SET VACATion HoLD  
(HoLD–To TiME AnD DATE)  
SET CURRENT TIME  
SET SCHEDULE  
BUTTON  
SET CURREnT DATE  
DonE BUTTon  
(EXiT MEnU)  
USER SySTEM SETTingS  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
61000762A 8800 Tstat Owners.indd  
5
3/28/11 4:20:01 PM  
OpERATION  
SElECT SySTEM MODE  
(EM HEAT/HEAT/OFF/COOL/AUTO)  
CHANGE TEMpERATURE SET pOINT  
press [MODE] to select:  
EM HEAT: (only for heat pumps with auxiliary heat)  
Thermostat controls auxiliary heat. Heat pump will not  
operate in EM HEAT mode.  
press  
or  
to adjust the current set point.  
(See Program Schedule Holds on pages 17-19 for more  
information.)  
HEAT: Thermostat controls only the heating system.  
Off: Heating and cooling systems are off.  
COOl: Thermostat controls only the cooling system.  
AUTO: (if enabled in installer setup) Thermostat  
automatically selects heating or cooling depending on  
the indoor temperature.  
press [DONE] to save and exit, or [CANCEl] to exit  
without saving. The thermostat will save and exit if  
nothing is pressed within 10 seconds.  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
61000762A 8800 Tstat Owners.indd  
6
3/28/11 4:20:01 PM  
OpERATION  
SElECT fAN SETTING (ON/AUTO/CIRC)  
ClEAN SCREEN  
When the fan mode is changed during a program event  
it remains in that mode until the next event starts. The  
fan must be programmed to FAn on in the schedule to  
run continuously through all events.  
press [MENU] to enter the main menu.  
press [ClEAN SCREEN] to disable the touch screen  
for 30 seconds for cleaning.  
Note: Use a soft damp cloth to clean the screen. Use  
water or household glass cleaner. Do not spray liquids  
directly on the screen.  
MAINTENANCE REMINDERS  
Maintenance reminders are set up by the installer to  
indicate when the equipment is due for service. if a  
maintenance reminder is displayed, call your HVAC  
dealer for service. They can be cleared by pressing  
[MENU] to enter the main menu, then [Next] to clear  
each reminder.  
press [fAN] to select:  
ON: Fan runs continuously. Use this mode for maximum  
air circulation/cleaning.  
AUTO: Fan runs only when the heating or cooling  
system is on.  
CIRC: Same as AUTo, but ensures the fan is on for at  
least 20 minutes per hour. Use this mode for a balance  
of energy savings and air circulation/cleaning.  
press [DONE] to save and exit, or [CANCEl] to exit  
without saving. The thermostat will save and exit if  
nothing is pressed within 10 seconds.  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
61000762A 8800 Tstat Owners.indd  
7
3/28/11 4:20:01 PM  
OpERATION  
bATTERy REplACEMENT  
Batteries are not required for proper operation. The  
thermostat is a 24VAC powered device with a battery  
back-up for the clock.  
RESET  
BUTTON  
The thermostat has a memory backup that saves the  
thermostat’s settings in case of a power interruption.  
The system settings will be retained but the clock will  
reset after 90 seconds with no battery or AC power.  
Replace the batteries every year or when the low  
battery indicator comes on.  
The reset button located under the battery cover can be  
used to reset the thermostat to factory defaults.  
wARNING  
The reset button should only be used by the installer.  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
61000762A 8800 Tstat Owners.indd  
8
3/28/11 4:20:02 PM  
HUMIDISTAT fUNCTIONS  
HUMIDISTAT CONTROl SCREEN  
The Model 8800 has the option of being configured as a humidistat that can control a humidifier and dehumidifier.  
Note: Humidistat mode is selected in the user setup menu.  
RooM RELATiVE HUMiDiTy  
RooM RELATiVE HUMiDiTy SETPoinT  
CURREnT DAy  
HUMiDiFiER ADJUSTMEnT  
MESSAGE  
CENTER  
(SCRoLLing TEXT)  
oUTDooR TEMPERATURE  
DEHUMiDiFiER ADJUSTMEnT  
nETwoRk oVERRiDE  
(iF EnABLED)  
CURRENT TIME  
& DATE  
MAIN MENU BUTTON  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
61000762A 8800 Tstat Owners.indd  
9
3/28/11 4:20:03 PM  
HUMIDISTAT fUNCTIONS  
HOw TO ENTER THE SETUp MENU TO CHANGE HUMIDISTAT MODE  
press [MENU] to enter the main menu.  
press [SETUp] to enter the setup menu.  
press  
flashes.)  
or  
to adjust the setting. (Selected option  
Press [DONE] to save and exit, or [CANCEl] to exit  
without saving.  
The thermostat will discard changes and exit if nothing  
is pressed within 60 seconds.  
press [Next] or [back] to page through the settings,  
until you get to the Humidistat Mode Setting (the  
setting is displayed in the message center).  
MESSAGE CENTER  
(SCRoLLing TEXT)  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
61000762A 8800 Tstat Owners.indd 10  
3/28/11 4:20:04 PM  
NETwORK fEATURES  
NETwORK OVERRIDE  
The network override feature is only available to be enabled when the thermostat is set to non-programmable mode  
or humidistat mode. when enabled, this feature can be used by pressing [HOlD].  
SECURITy  
A four digit security Pin can be enabled to restrict access to the system. if you forget your Pin, you can access the  
thermostat with the master PIN 7777.  
STATUS INDICATORS  
The status indicator is located at the top of the screen. when the thermostat sends or receives messages, the  
bars flash across the screen. The message center will display “COMMUNICATION LOST” if the thermostat has not  
received communications in the last 15 minutes.  
BARS FLASH  
ACROSS SCREEN  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
61000762A 8800 Tstat Owners.indd 11  
3/28/11 4:20:04 PM  
pROGRAMMING  
SET TIME  
SET DATE  
press [MENU] to enter the main menu.  
press [SET ClOCK] to enter clock menu.  
press [MENU] to enter the main menu.  
press [SET DATE] to enter date menu.  
press  
or  
to set the hour.  
press  
or  
to set the month.  
press [Next], then  
or  
to set the minute.  
press [Next], then  
press [Next], then  
or  
or  
to set the day.  
to set the year.  
press [DONE] to save and exit, or [CANCEl] to exit  
without saving. The thermostat will save and exit if  
nothing is pressed within 20 seconds.  
press [DONE] to save and exit, or [CANCEl] to exit  
without saving. The thermostat will save and exit if  
nothing is pressed within 20 seconds.  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
61000762A 8800 Tstat Owners.indd 12  
3/28/11 4:20:05 PM  
pROGRAMMING  
UNDERSTANDING pROGRAM SCHEDUlES  
The daily schedule is split into four events:  
wAKE: temperature you would prefer to wake up to.  
lEAVE: temperature when you are away from the house.  
RETURN: temperature you would prefer to return home to.  
SlEEp: temperature you would prefer while sleeping.  
The times shown in the table below are the defaults. The start time and temperature of each section can be changed  
to fit your schedule. (See Changing Program Schedules section on pages 15-16.)  
This thermostat is pre-set to use the following program settings recommended by the Department of Energy  
(see table below). These settings are intended to reduce your heating/cooling expenses. The fan program is pre-set  
to AUTO for all events.  
Set temperature  
Event designator  
WAKE  
Start time  
6:00AM  
8:00AM  
5:00PM  
Heat  
Cool  
fan  
70°F (21°C)  
62°F (17°C)  
70°F (21°C)  
62°F (17°C)  
78°F (26°C)  
85°F (29°C)  
78°F (26°C)  
82°F (28°C)  
AUTO  
AUTO  
AUTO  
AUTO  
LEAVE  
RETURN  
SLEEP  
10:00PM  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
61000762A 8800 Tstat Owners.indd 13  
3/28/11 4:20:05 PM  
pROGRAMMING  
UNDERSTANDING pROGRAM SCHEDUlES (CONTINUED)  
optionally, the thermostat can be set to a two event or commercial schedule. (See Setup Menu on page 20.)  
Set temperature  
Event designator  
wAkE/oCCUPiED  
LEAVE/UnoCCUPiED  
Start time  
6:00AM  
Heat  
Cool  
fan  
70°F (21°C)  
62°F (17°C)  
78°F (26°C)  
82°F (28°C)  
AUTO  
AUTO  
10:00PM  
pROGRESSIVE RECOVERy  
The Progressive Recovery feature allows the thermostat to activate the heating and cooling equipment prior to an  
event in order to reach the desired temperature at the start of the next scheduled event.  
Example: if the wAkE time is 6 am, and the temperature is 70°, the heat will come on before 6 am, so the  
temperature is 70° by the time you wake at 6 am.  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
61000762A 8800 Tstat Owners.indd 14  
3/28/11 4:20:06 PM  
pROGRAMMING  
CHANGING pROGRAM SCHEDUlES  
press [MENU] to enter the main menu.  
press [Next], then  
the first event.  
or  
to set the start time of  
press [SET SCHEDUlE] to enter schedule programming.  
press  
or  
to select the day.  
press [Next], then  
or  
to set the setpoints of the first event.  
Note: This step is not displayed for weekday/weekend  
schedules.  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
61000762A 8800 Tstat Owners.indd 15  
3/28/11 4:20:06 PM  
pROGRAMMING  
CHANGING pROGRAM SCHEDUlES (CONTINUED)  
press [Next], then [fAN] to set the fan mode of the  
The thermostat will display the CoPy option.  
first event.  
press [COpy] to copy the schedule of the day just  
programmed to any other day.  
press [Next] to advance to the next event.  
Repeat above process for each remaining event.  
press [DONE] to save the schedule for the day.  
OR  
press [CANCEl] to proceed to the next day and repeat  
the above process.  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
61000762A 8800 Tstat Owners.indd 16  
3/28/11 4:20:07 PM  
pROGRAMMING  
pROGRAM SCHEDUlE HOlDS – TEMpORARy  
TEMpORARy pROGRAM HOlD  
press  
or  
to adjust the end time of the hold. if  
end time is not adjusted, the Temporary Hold will end at  
the start of the next event.  
press  
or  
to immediately adjust the temperature  
when the schedule is running. This will temporarily hold  
the temperature setting until the next scheduled event.  
To cancel the Temporary Hold, press [CANCEl HOlD].  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
61000762A 8800 Tstat Owners.indd 17  
3/28/11 4:20:07 PM  
pROGRAMMING  
pROGRAM SCHEDUlE HOlDS pERMANENT  
pERMANENT pROGRAM HOlD  
pROGRAM SCHEDUlE HOlDS – VACATION  
VACATION pROGRAM HOlD  
press [HOlD] to permanently hold the temperature at  
its current setting while the schedule is running. This  
will override the temperature settings for all events.  
with the thermostat in Permanent Hold, the temperature  
setting and fan mode can be adjusted and will stay at  
that setting until the hold is cancelled.  
This energy saving feature allows you to suspend the  
programmed schedule for extended periods of time. The  
temperature you select will be maintained 24 hours a  
day until the vacation program hold end date and time.  
once the end date and time have been surpassed, the  
previously programmed schedule will resume. If you  
return earlier than expected, press [CANCEl HOlD] to  
resume the programmed schedule.  
press [MENU] to enter  
the main menu.  
press [SET VACATION]  
to enter vacation  
program hold.  
press  
or  
to adjust the  
temperature setting.  
To cancel the Permanent Hold, press [CANCEl HOlD].  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
61000762A 8800 Tstat Owners.indd 18  
3/28/11 4:20:08 PM  
pROGRAMMING  
pROGRAM SCHEDUlE HOlDS – VACATION (CONTINUED)  
VACATION pROGRAM HOlD (continued)  
press [Next], then [fAN] to set the fan mode.  
press [Next], then  
or  
to set end date.  
press [Next], then  
or  
to set end time.  
press [DONE] to save and exit, or [CANCEl] to exit  
without saving. The thermostat will save and exit if  
nothing is pressed within 20 seconds.  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
61000762A 8800 Tstat Owners.indd 19  
3/28/11 4:20:09 PM  
SETUp MENU  
HOw TO ENTER THE SETUp MENU TO CHANGE SETTINGS  
press [MENU] to enter the main menu.  
press [SETUp] to enter the setup menu.  
press  
flashes.)  
or  
to adjust the setting. (Selected option  
Press [DONE] to save and exit, or [CANCEl] to exit  
without saving.  
The thermostat will discard changes and exit if nothing  
is pressed within 60 seconds.  
press [Next] or [back] to page through the settings  
(the setting is displayed in the message center).  
MESSAGE CENTER  
(SCRoLLing TEXT)  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
61000762A 8800 Tstat Owners.indd 20  
3/28/11 4:20:09 PM  
SETUp MENU  
USER SySTEM SETTINGS TAblE  
The following table is the list of the settings and their details. Default settings are shown in bold.  
System setting  
HUMiDiSTAT MoDE  
Description  
factory default setting (bold) and setting range  
(only available if controller type  
is set to humidistat)  
HUMiDiFy  
DEHUMiDiFy  
AUTO  
Off  
TEMPERATURE SCALE Set the thermostat to Fahrenheit fAHRENHEIT  
or Celsius mode  
CELSIUS  
AUTo DAyLigHT  
SAVINGS  
Enable or disable auto daylight  
savings  
MARCH – Second Sunday in March to the first Sunday  
in November  
APRiL – First Sunday in April to the last Sunday in october  
oFF  
BACkLigHT inTEnSiTy Backlight intensity as a  
100 pERCENT  
Selection of 0 – 100%  
percentage of full on  
EVEnTS PER DAy  
SECURiTy  
Number of program events  
per day  
fOUR EVENTS pER DAy  
Two EVEnTS PER DAy  
Enable PIN code security feature DISAblED  
(only available if enabled in  
installer setup)  
EnABLED  
SECURiTy Pin  
Sets security PIN code. The  
thermostat can also be accessed 4-digit numeric PIN  
with the master PIN 7777 (only  
####  
available if Security is enabled)  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
61000762A 8800 Tstat Owners.indd 21  
3/28/11 4:20:09 PM  
SETUp MENU  
USER SySTEM SETTINGS TAblE (CONTINUED)  
System setting  
LoCkoUT TyPE  
Description  
factory default setting (bold) and setting range  
Level of lockout (only  
available if Security is  
enabled)  
Off: No lockout  
PARTIAL lockout  
FULL lockout  
MoDE LoCkoUT  
FAn LoCkoUT  
System mode lockout  
Off: No lockout  
setting (only available in FULL: no system mode changes allowed  
partial lockout)  
Fan mode lockout setting Off: No lockout  
(only available in partial  
lockout)  
TiMED: changes revert after temporary change period  
FULL: no fan mode changes allowed  
SETPOINT LOCKOUT  
Setpoint lockout setting  
(only available in partial  
lockout)  
Off: No lockout  
TiME-LiMiTED: changes revert after temporary change period  
RAngE-LiMiTED: set by max setpoint lockout  
TiME AnD RAngE: set by max setpoint lockout and temporary change period  
FULL: no setpoint changes allowed  
MAX SETPoinT  
CHANGE IN LOCKOUT for temperature and  
humidity adjustments  
Setpoint range limit  
5° f or C, 5% RH  
oFF to ±20° F or C, oFF to ±20% RH  
(only available in partial  
lockout)  
TEMPoRARy CHAngE Time-limited lockout  
PERioD  
60 MINUTES  
temporary change period 0 to 255 MINUTES  
(only available in partial  
lockout)  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
61000762A 8800 Tstat Owners.indd 22  
3/28/11 4:20:09 PM  
THERMOSTAT fIVE yEAR lIMITED wARRANTy  
your Research Products Corporation Aprilaire® Thermostat unit is expressly warranted for five (5) years from date of installation to be free from  
defects in materials or workmanship.  
Research Products Corporation’s exclusive obligation under this warranty shall be to supply, without charge, a replacement for any thermostat  
which is found to be defective within such five (5) year period and which is returned, together with the date of installation, no later than thirty (30)  
days after said five (5) year period by you to either your original supplier or to Research Products Corporation, Madison, wisconsin 53701.  
THiS wARRAnTy SHALL noT oBLigATE RESEARCH PRoDUCTS CoRPoRATion FoR Any LABoR CoSTS AnD SHALL noT APPLy To DEFECTS in  
woRkMAnSHiP oR MATERiALS FURniSHED By yoUR inSTALLER AS ConTRASTED To DEFECTS in THE THERMoSTAT iTSELF.  
iMPLiED wARRAnTiES oF MERCHAnTABiLiTy oF FiTnESS FoR A PARTiCULAR PURPoSE SHALL BE LiMiTED in DURATion To THE AFoRESAiD  
FiVE yEAR PERioD. RESEARCH PRoDUCTS CoRPoRATion’S LiABiLiTy FoR inCiDEnTAL oR ConSEQUEnTiAL DAMAgES, oTHER THAn  
DAMAgES FoR PERSonAL inJURiES, RESULTing FRoM Any BREACH oF THE AFoRESAiD iMPLiED wARRAnTiES oR THE ABoVE LiMiTED  
wARRAnTy iS EXPRESSLy EXCLUDED. THiS LiMiTED wARRAnTy iS VoiD iF DEFECT(S) RESULT FRoM FAiLURE To HAVE THiS THERMoSTAT  
inSTALLED By A QUALiFiED HEATing AnD AiR ConDiTioning ConTRACToR. iF THE LiMiTED wARRAnTy iS VoiD DUE To FAiLURE To USE A  
QUALiFiED ConTRACToR, ALL DiSCLAiMERS oF iMPLiED wARRAnTiES SHALL BE EFFECTiVE UPon inSTALLATion.  
Some states do not allow limitations on how long an implied warranty lasts or the exclusion or limitation of incidental or consequential damages,  
so the above exclusions or limitations may not apply to you.  
This warranty gives you specific legal rights and you may also have other rights which vary from state to state.  
This equipment if installed in strict accordance with the manufacturer’s instructions, complies with the limits for a Class B computing device  
pursuant to Subpart J of Part 15 of FCC Rules.  
wARRANTy REGISTRATION  
if you do not have on-line access, please mail a postcard with your name, address, phone number, product purchased  
and date of purchase to: Research Products Corporation, P.o. BoX 1467, Madison, wi 53701  
your warranty Registration information will not be sold or shared outside of this company.  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
61000762A 8800 Tstat Owners.indd 23  
3/28/11 4:20:10 PM  
P.o. Box 1467 • Madison, wi 53701-1467 • Phone: 800/334-6011 • Fax: 608/257-4357  
www.aprilaire.com  
61000762 3.11  
B2205383A  
© 2011 Aprilaire – A division of Research Products Corporation  
Download from Www.Somanuals.com. All Manuals Search And Download.  
61000762A 8800 Tstat Owners.indd 24  
3/28/11 4:20:10 PM  